OVHcloud Network Status

Current status
Legend
  • Operational
  • Degraded performance
  • Partial Outage
  • Major Outage
  • Under maintenance
GRA<>BRU
Scheduled Maintenance Report for Network & Infrastructure
Completed
Nous ajoutons 1x100G entre notre datacentre de Gravelines et le POP de Bruxelles.

Update(s):

Date: 2017-01-18 13:21:12 UTC
Tout est ok, le lien 100G GRA <> BRU est opérationnel.

Date: 2017-01-18 12:20:25 UTC
Le lien GRA <> BRU est proddé, nous avons environ 6G / 1,5G de trafic dessus et aucun CRC

bru-1-a72#sh int eth 51/1 | i rate|CRC
30 seconds input rate 6.26 Gbps (6.4% with framing overhead), 828342 packets/sec
30 seconds output rate 1.71 Gbps (1.8% with framing overhead), 586503 packets/sec
0 input errors, 0 CRC, 0 alignment, 0 symbol, 0 input discards

gra-d2-a75(s1)#sh int Et7/7/1 | i rate|CRC
30 seconds input rate 1.73 Gbps (1.8% with framing overhead), 599134 packets/sec
30 seconds output rate 6.36 Gbps (6.5% with framing overhead), 841265 packets/sec
0 input errors, 0 CRC, 0 alignment, 0 symbol, 0 input discards


Nous monitorons.
Posted Jan 18, 2017 - 11:14 UTC