FS#3150 — rbx-43
Attached to Project— Reseau Internet et Baies
| Incident | |
| Tout le réseau | |
| CLOSED | |
![]() |
Le routeur a quelques problemes de syncronisation des messages
entre plusieurs cartes.
Jun 12 07:55:37 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:33 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 5 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:40 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:36 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 1 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:40 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:36 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 2 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:40 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:36 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 5 (asic=2, srcidx=0xffff, seq=31)
Jun 12 07:55:41 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:37 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 2 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:41 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:37 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 5 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:41 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:37 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 1 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:41 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:37 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 5 (asic=2, srcidx=0xffff, seq=31)
Date: Tuesday, 16 June 2009, 09:45AMentre plusieurs cartes.
Jun 12 07:55:37 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:33 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 5 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:40 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:36 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 1 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:40 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:36 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 2 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:40 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:36 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 5 (asic=2, srcidx=0xffff, seq=31)
Jun 12 07:55:41 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:37 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 2 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:41 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:37 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 5 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:41 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:37 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 1 (asic=1, srcidx=0x0, seq=0)
Jun 12 07:55:41 rbx-43-c1.routers.ovh.net 2009 Jun 12 05:55:37 %SYS-1-MOD_SEQMISMATCH:Bus asic sequence mismatch occurred on module 5 (asic=2, srcidx=0xffff, seq=31)
Reason for closing: Done
RSS for all categories

il a basculé de carte de routage vers #2.
Après le redemarrage de la carte #1 pour l'instant tout va bien.
Nous avons de nouveau des problèmes sur ce chassis. Nous faisons un redémarrage sur la carte #1 uniquement
Le routeur est pour l'instant stable sur la carte #1. Nous allons pour l'instant tourner sur cette carte uniquement et vérifier que c'est bien cette carte qui posait problème.
Nous remplacons la carte #2
Nous avons observé les mêmes symptomes que précédemment et coupé la carte #1 pour éviter d'autres problèmes. C'est cette carte qui pose en fait problème. Nous allons donc la remplacer également. Le routeur fonctionne pour l'instant sur la carte #2 uniquement.