Le filer a redémarré alors que nous remplacions un disque.

Date:  Wednesday, 08 July 2009, 14:41PM
Reason for closing:  Done
Comment by OVH - Wednesday, 08 July 2009, 11:09AM

Jul 8 10:53:57 filerz48 savecore: [ID 570001 auth.error] reboot after panic: ZFS: I/O failure (read on <unknown> off 0: zio fffffe840796b980 [L0 zvol object] 2000L/2000P DVA[0]=<10:d3587a000:2000> fletcher2 unco
mpressed LE contiguous birth=3362192 fill=1 cksum=1c70c7cd5d085d1
Jul 8 10:53:57 filerz48 savecore: [ID 748169 auth.error] saving system crash dump in /var/crash/unknown/*.0


Comment by OVH - Wednesday, 08 July 2009, 11:14AM

Nous avons retiré le mauvais disque dur du pool suite à une erreur humaine. Le filer a rebooté.

Le filer est en cours de demarrage et les données sont en train d'être montées.


Comment by OVH - Wednesday, 08 July 2009, 12:45PM

Le serveur iscsi est maintenant fonctionnel.
Nous avons changé le disque cassé par un spare. La reconstruction du raid est en cours et peu être à l'origine de certains ralentissements.