FS#33523 — software on switch baie n3 (TOR): XXX-sdtorYY-n3

Attached to Project— Reseau Internet et Baies
Maintenance
Tout le réseau
CLOSED
100%
In order to improve stability and performances, we plan to do a software upgrade on the following switches.
To minimise service interruption, maintenances will be done when the bandwidth usage is the lower.
Each switch upgrade can generate up to 5mn of traffic perturbation.

### DONE

gra1-sdtor11a-n3_gra1-sdtor11b-n3
gra1-sdtor13a-n3_gra1-sdtor13b-n3
gra1-sdtor22a-n3_gra1-sdtor22b-n3
gra1-sdtor28a-n3_gra1-sdtor28b-n3
gra1-sdtor17a-n3_gra1-sdtor17b-n3
gra1-sdtor14a-n3_gra1-sdtor14b-n3
gra1-sdtor16a-n3_gra1-sdtor16b-n3
gra1-sdtor12a-n3_gra1-sdtor12b-n3
gra1-sdtor18a-n3_gra1-sdtor18b-n3
gra1-sdtor19a-n3_gra1-sdtor19b-n3
gra1-sdtor29a-n3_gra1-sdtor29b-n3
gra1-sdtor31a-n3_gra1-sdtor31b-n3
gra1-sdtor20a-n3_gra1-sdtor20b-n3
gra1-sdtor21a-n3_gra1-sdtor21b-n3
gra1-sdtor23a-n3_gra1-sdtor23b-n3
gra1-sdtor26a-n3_gra1-sdtor26b-n3
gra1-sdtor27a-n3_gra1-sdtor27b-n3
gra1-sdtor30a-n3_gra1-sdtor30b-n3
rbx6-sdtor1a-n3_rbx6-sdtor1b-n3
gra1-sdtor32a-n3_gra1-sdtor32b-n3
gra1-sdtor9a-n3_gra1-sdtor9b-n3
rbx6-sdtor15a-n3_rbx6-sdtor15b-n3
rbx6-sdtor16a-n3_rbx6-sdtor16b-n3
rbx6-sdtor18a-n3_rbx6-sdtor18b-n3
rbx6-sdtor21a-n3_rbx6-sdtor21b-n3
rbx6-sdtor19a-n3_rbx6-sdtor19b-n3
rbx6-sdtor20a-n3_rbx6-sdtor20b-n3
rbx6-sdtor4a-n3_rbx6-sdtor4b-n3
rbx6-sdtor22a-n3_rbx6-sdtor22b-n3
rbx6-sdtor3a-n3_rbx6-sdtor3b-n3
rbx6-sdtor5a-n3_rbx6-sdtor5b-n3


The following switches will be done in a next batch :

gra1-sdtor15a-n3_gra1-sdtor15b-n3
gra1-sdtor24a-n3_gra1-sdtor24b-n3
gra1-sdtor25a-n3_gra1-sdtor25b-n3

Date:  Friday, 14 September 2018, 11:00AM
Reason for closing:  
Comment by OVH - Tuesday, 21 August 2018, 05:11AM

we are starting the maintenance for gra1-sdtor13a-n3


Comment by OVH - Tuesday, 21 August 2018, 06:17AM

gra1-sdtor13a-n3 and gra1-sdtor11b-n3 done


Comment by OVH - Tuesday, 28 August 2018, 03:14AM

We will start maintenance on gra1-sdtor22a-n3


Comment by OVH - Tuesday, 28 August 2018, 03:46AM

We finished gra1-sdtor22a-n3 and continue on the B.


Comment by OVH - Tuesday, 28 August 2018, 03:59AM

We will start maintenance on gra1-sdtor28a-n3


Comment by OVH - Tuesday, 28 August 2018, 04:08AM

gra1-sdtor22b-n3 is now completed.


Comment by OVH - Tuesday, 28 August 2018, 04:18AM

gra1-sdtor28a-n3 is back online, we will start the maintenance on the B.


Comment by OVH - Tuesday, 28 August 2018, 04:31AM

gra1-sdtor28b-n3 is now back online. The maintenance is now finished.


Comment by OVH - Tuesday, 28 August 2018, 05:22AM

The maintenance on gra1-sdtor17a-n3 and-sdtor17b-n3 has started.


Comment by OVH - Tuesday, 28 August 2018, 05:31AM

The maintenance on gra1-sdtor14a-n3 and-sdtor14b-n3 has started.


Comment by OVH - Tuesday, 28 August 2018, 05:58AM

The maintenance on gra1-sdtor14a-n3 and-sdtor14b-n3 is done, switches are upgraded.
We start the upgrade on gra1-sdtor16a-n3_gra1-sdtor16b-n3.


Comment by OVH - Tuesday, 28 August 2018, 06:21AM

The maintenance on gra1-sdtor17a-n3 and-sdtor17b-n3 is done, switches are upgraded.
We start the upgrade on gra1-sdtor12a-n3_gra1-sdtor12b-n3.


Comment by OVH - Tuesday, 28 August 2018, 06:53AM

The maintenance on gra1-sdtor16a-n3 and-sdtor16b-n3 is done, switches are upgraded.


Comment by OVH - Tuesday, 28 August 2018, 06:58AM

We start the upgrade on gra1-sdtor18a-n3_gra1-sdtor18b-n3.


Comment by OVH - Tuesday, 28 August 2018, 07:18AM

The maintenance on gra1-sdtor16a-n3 and gra1-sdtor16b-n3 is done, switches are upgraded.


Comment by OVH - Tuesday, 28 August 2018, 07:30AM

The maintenance on gra1-sdtor12a-n3 and-sdtor12b-n3 is done, switches are upgraded.
The maintenance on gra1-sdtor18a-n3 and-sdtor18b-n3 is done, switches are upgraded.
We start the upgrade on gra1-sdtor19a-n3_gra1-sdtor19b-n3.


Comment by OVH - Tuesday, 28 August 2018, 08:16AM

The maintenance on gra1-sdtor19a-n3 and gra1-sdtor19b-n3 is done, switches are upgraded.


Comment by OVH - Wednesday, 29 August 2018, 01:51AM

We will begin the maintenance in 10 minutes on gra1-sdtor29b-n3


Comment by OVH - Wednesday, 29 August 2018, 02:03AM

Ongoing update on gra1-sdtor29b-n3


Comment by OVH - Wednesday, 29 August 2018, 02:14AM

gra1-sdtor29b-n3 is done, we will process on the A side.


Comment by OVH - Wednesday, 29 August 2018, 02:34AM

Both gra1-sdtor29a/b-n3 has been done successfully.


Comment by OVH - Wednesday, 29 August 2018, 02:57AM

We will start maintenance on gra1-sdtor31a-n3


Comment by OVH - Wednesday, 29 August 2018, 03:15AM

The switch rebooted before the maintenance, we will update the switch NOW.


Comment by OVH - Wednesday, 29 August 2018, 03:38AM

We will proceed on the B side now.


Comment by OVH - Wednesday, 29 August 2018, 03:51AM

The switch gra1-sdtor31b-n3 is also updated now. The maintenance is finished.


Comment by OVH - Wednesday, 29 August 2018, 05:11AM

We start the upgrade on gra1-sdtor20a-n3_gra1-sdtor20b-n3.


Comment by OVH - Wednesday, 29 August 2018, 05:35AM

We start the upgrade on gra1-sdtor21a-n3_gra1-sdtor21b-n3.


Comment by OVH - Wednesday, 29 August 2018, 06:00AM

We start the upgrade on gra1-sdtor23a-n3_gra1-sdtor23b-n3.


Comment by OVH - Wednesday, 29 August 2018, 06:19AM

The maintenance on gra1-sdtor20a-n3 and gra1-sdtor20b-n3 is done, switches are upgraded.


Comment by OVH - Wednesday, 29 August 2018, 06:30AM

The maintenance on gra1-sdtor21a-n3 and gra1-sdtor21b-n3 is done, switches are upgraded.
We start the upgrade on gra1-sdtor26a-n3_gra1-sdtor26b-n3.


Comment by OVH - Wednesday, 29 August 2018, 06:39AM

The maintenance on gra1-sdtor23a-n3 and gra1-sdtor23b-n3 is done, switches are upgraded.


Comment by OVH - Wednesday, 29 August 2018, 07:01AM

We start the upgrade on gra1-sdtor27a-n3_gra1-sdtor27b-n3.


Comment by OVH - Wednesday, 29 August 2018, 07:30AM

The maintenance on gra1-sdtor26a-n3 and gra1-sdtor26b-n3 is done, switches are upgraded.
We start the upgrade on gra1-sdtor30a-n3_gra1-sdtor30b-n3.


Comment by OVH - Wednesday, 29 August 2018, 07:38AM

gra1-sdtor27a-n3 is upgraded.
gra1-sdtor27b-n3 crashed during the upgrade, we are checking on this.


Comment by OVH - Wednesday, 29 August 2018, 07:43AM

The maintenance on gra1-sdtor30a-n3 and gra1-sdtor30b-n3 is done, switches are upgraded.

gra1-sdtor27b-n3 has been replaced.


Comment by OVH - Thursday, 30 August 2018, 02:59AM

We will proceed with the upgrade of rbx6-sdtor1a/b-n3.


Comment by OVH - Thursday, 30 August 2018, 03:18AM

The update is finished,.


Comment by OVH - Thursday, 30 August 2018, 05:03AM

We start the upgrade on gra1-sdtor32a-n3_gra1-sdtor32b-n3.


Comment by OVH - Thursday, 30 August 2018, 05:15AM

The maintenance on gra1-sdtor32a-n3 and gra1-sdtor32b-n3 is done, switches are upgraded.


Comment by OVH - Thursday, 30 August 2018, 05:30AM

We start the upgrade on gra1-sdtor9a-n3_gra1-sdtor9b-n3.


Comment by OVH - Thursday, 30 August 2018, 06:00AM

The maintenance on gra1-sdtor9a-n3_gra1-sdtor9b-n3 is done, switches are upgraded.
We start the upgrade on rbx6-sdtor15a-n3_rbx6-sdtor15b-n3.


Comment by OVH - Thursday, 30 August 2018, 06:08AM

The maintenance on rbx6-sdtor15a-n3 and rbx6-sdtor15b-n3 is done, switches are upgraded.


Comment by OVH - Thursday, 30 August 2018, 06:30AM

We start the upgrade on rbx6-sdtor16a-n3_rbx6-sdtor16b-n3.


Comment by OVH - Thursday, 30 August 2018, 06:39AM

The maintenance on rbx6-sdtor16a-n3_rbx6-sdtor16b-n3 is done, switches are upgraded.


Comment by OVH - Thursday, 30 August 2018, 07:00AM

We start the upgrade on rbx6-sdtor18a-n3_rbx6-sdtor18b-n3.


Comment by OVH - Thursday, 30 August 2018, 07:10AM

The maintenance on rbx6-sdtor18a-n3_rbx6-sdtor18b-n3 is done, switches are upgraded.


Comment by OVH - Thursday, 30 August 2018, 07:30AM

We start the upgrade on rbx6-sdtor21a-n3_rbx6-sdtor21b-n3.


Comment by OVH - Thursday, 30 August 2018, 07:37AM

The maintenance on rbx6-sdtor21a-n3 and rbx6-sdtor21b-n3 is done, switches are upgraded.


Comment by OVH - Friday, 31 August 2018, 01:26AM

We will start maintenance on rbx6-sdtor19a/b-n3.


Comment by OVH - Friday, 31 August 2018, 01:42AM

Maintenance is finished for rbx6-sdtor19a/b-n3


Comment by OVH - Friday, 31 August 2018, 02:47AM

We will proceed with the maintenance of rbx6-sdtor20ab-n3.


Comment by OVH - Friday, 31 August 2018, 03:00AM

Maintenance is now finished on rbx6-sdtor20ab-n3.


Comment by OVH - Monday, 03 September 2018, 06:24AM

We will proceed with the maintenance of rbx6-sdtor4ab-n3.


Comment by OVH - Monday, 03 September 2018, 07:16AM

The B upgrade takes longer than expected.


Comment by OVH - Monday, 03 September 2018, 07:56AM

Maintenance is now finished on rbx6-sdtor4ab-n3.


Comment by OVH - Tuesday, 04 September 2018, 12:07PM

Nous allons procéder à la mise à jour urgente de tous les équipements top of rack impactés par un bug logiciel à SBG et une partie à WAW.
L'impact maximum prévu par baie est une coupure de trafic de 10 min maximum.
La période de maintenance s'étale de de 23:00 UTC+2 à 02:30 UTC+2.

Les informations sur cette opération sont disponibles dans la tâche suivante : http://travaux.ovh.net/?do=details&id=33908

---

We're going to proceed with an emergency software upgrade on every top of rack devices impacted by a software bug, located in SBG and a part in WAW.
The maximum expected impact is a 10 min traffic disruption.
Maintenance window starts at 23:00 UTC+2 and ends at 02:30 UTC+2.

Details are available in the following task : http://travaux.ovh.net/?do=details&id=33908


Comment by OVH - Tuesday, 04 September 2018, 17:20PM

Nous allons procéder à la mise à jour urgente de tous les équipements top of rack impactés par un bug logiciel à BHS.
L'impact maximum prévu par baie est une coupure de trafic de 10 min maximum.
La période de maintenance s'étale de 09:00 UTC+2 à 12:00 UTC+2, ce 5 Septembre 2018.

Les informations sur cette opération sont disponibles dans la tâche suivante : https://travaux.ovh.net/?do=details&id=33923

---

We're going to proceed with an emergency software upgrade on every top of rack devices impacted by a software bug, located in BHS.
The maximum expected impact is a 10 min traffic disruption.
Maintenance window starts at 09:00 UTC+2 and ends at 12:00 UTC+2, on the 5th of September.


Details are available in the following task : https://travaux.ovh.net/?do=details&id=33923


Comment by OVH - Wednesday, 05 September 2018, 18:14PM

Nous allons procéder à la mise à jour urgente de tous les équipements top of rack impactés par un bug logiciel à SGP et SYD.
L'impact maximum prévu par baie est une coupure de trafic de 10 min maximum.
La période de maintenance s'étale de 15:30 UTC à 18:30 UTC, ce 6 Septembre 2018.

Les informations sur cette opération sont disponibles dans les tâches suivantes :
https://travaux.ovh.net/?do=details&id=33955
https://travaux.ovh.net/?do=details&id=33956

---

We're going to proceed with an emergency software upgrade on every top of rack devices impacted by a software bug, located in SGP and SYD.
The maximum expected impact is a 10 min traffic disruption.
Maintenance window starts at 15:30 UTC and ends at 18:30 UTC, on the 6th of September.


Details are available in the following tasks :
https://travaux.ovh.net/?do=details&id=33955
https://travaux.ovh.net/?do=details&id=33956