FS#4978 — rbx-97-n7 N7K-C7018-FAB-1
Attached to Project— Reseau Internet et Baies
| Maintenance | |
| Tout le réseau | |
| CLOSED | |
![]() |
Nous allons inserer les 2 nouvelles fabric pour ajouter
en suite de nouvelles cartes.
rbx-97-n7# sh environment power
Power Supply:
Voltage: 50 Volts
Power Actual Total
Supply Model Output Capacity Status
(Watts ) (Watts )
------- ------------------- ----------- ----------- --------------
1 ------------ 0 W 0 W Absent
2 N7K-AC-6.0KW 1004 W 6000 W Ok
3 ------------ 0 W 0 W Absent
4 N7K-AC-6.0KW 1015 W 6000 W Ok
Actual Power
Module Model Draw Allocated Status
(Watts ) (Watts )
------- ------------------- ----------- ----------- --------------
1 N7K-M148GS-11L 271 W 400 W Powered-Up
2 N7K-M108X2-12L 486 W 650 W Powered-Up
3 N7K-M132XP-12 N/A 750 W Powered-Up
9 N7K-SUP1 N/A 210 W Powered-Up
10 N7K-SUP1 N/A 210 W Powered-Up
Xb1 N7K-C7018-FAB-1 N/A 100 W Powered-Up
Xb2 N7K-C7018-FAB-1 N/A 100 W Powered-Up
Xb3 N7K-C7018-FAB-1 N/A 100 W Powered-Up
Xb4 xbar N/A 100 W Absent
Xb5 xbar N/A 100 W Absent
fan1 N7K-C7018-FAN 217 W 736 W Powered-Up
fan2 N7K-C7018-FAN 189 W 537 W Powered-Up
N/A - Per module power not available
Power Usage Summary:
--------------------
Power Supply redundancy mode (configured) PS-Redundant
Power Supply redundancy mode (operational) PS-Redundant
Total Power Capacity (based on configured mode) 6000 W
Total Power of all Inputs (cumulative) 12000 W
Total Power Output (actual draw) 2019 W
Total Power Allocated (budget) 3993 W
Total Power Available for additional modules 2007 W
Date: Tuesday, 28 December 2010, 17:19PMen suite de nouvelles cartes.
rbx-97-n7# sh environment power
Power Supply:
Voltage: 50 Volts
Power Actual Total
Supply Model Output Capacity Status
(Watts ) (Watts )
------- ------------------- ----------- ----------- --------------
1 ------------ 0 W 0 W Absent
2 N7K-AC-6.0KW 1004 W 6000 W Ok
3 ------------ 0 W 0 W Absent
4 N7K-AC-6.0KW 1015 W 6000 W Ok
Actual Power
Module Model Draw Allocated Status
(Watts ) (Watts )
------- ------------------- ----------- ----------- --------------
1 N7K-M148GS-11L 271 W 400 W Powered-Up
2 N7K-M108X2-12L 486 W 650 W Powered-Up
3 N7K-M132XP-12 N/A 750 W Powered-Up
9 N7K-SUP1 N/A 210 W Powered-Up
10 N7K-SUP1 N/A 210 W Powered-Up
Xb1 N7K-C7018-FAB-1 N/A 100 W Powered-Up
Xb2 N7K-C7018-FAB-1 N/A 100 W Powered-Up
Xb3 N7K-C7018-FAB-1 N/A 100 W Powered-Up
Xb4 xbar N/A 100 W Absent
Xb5 xbar N/A 100 W Absent
fan1 N7K-C7018-FAN 217 W 736 W Powered-Up
fan2 N7K-C7018-FAN 189 W 537 W Powered-Up
N/A - Per module power not available
Power Usage Summary:
--------------------
Power Supply redundancy mode (configured) PS-Redundant
Power Supply redundancy mode (operational) PS-Redundant
Total Power Capacity (based on configured mode) 6000 W
Total Power of all Inputs (cumulative) 12000 W
Total Power Output (actual draw) 2019 W
Total Power Allocated (budget) 3993 W
Total Power Available for additional modules 2007 W
Reason for closing: Done
RSS for all categories

2010 Dec 28 17:04:55 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Fabric-Module 4 current-status is MOD_STATUS_ERRDOWN
2010 Dec 28 17:04:55 rbx-97-n7 %PLATFORM-2-XBAR_PWRFAIL_EJECTORS_OPEN: Both ejectors open, Xbar 4 will not be powered up (Serial number JAF1446AEAH)
2010 Dec 28 17:04:58 rbx-97-n7 %PLATFORM-2-XBAR_DETECT: Xbar 4 detected (Serial number JAF1446AEAH)
2010 Dec 28 17:04:58 rbx-97-n7 %PLATFORM-5-XBAR_PWRUP: Xbar 4 powered up (Serial number JAF1446AEAH)
2010 Dec 28 17:04:58 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Fabric-Module 4 current-status is MOD_STATUS_POWERED_UP
2010 Dec 28 17:05:11 rbx-97-n7 %MODULE-5-XBAR_OK: Xbar 4 is online (serial: JAF1446AEAH)
2010 Dec 28 17:05:11 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Fabric-Module 4 current-status is MOD_STATUS_ONLINE/OK
2010 Dec 28 17:06:53 rbx-97-n7 %PLATFORM-3-EJECTOR_STAT_CHANGED: Ejectors' status in slot 22 has changed, Top Ejector is OPEN, Bottom Ejector is CLOSE
2010 Dec 28 17:06:59 rbx-97-n7 %PLATFORM-3-EJECTOR_STAT_CHANGED: Ejectors' status in slot 19 has changed, Top Ejector is OPEN, Bottom Ejector is CLOSE
2010 Dec 28 17:06:59 rbx-97-n7 %PLATFORM-3-EJECTOR_STAT_CHANGED: Ejectors' status in slot 20 has changed, Top Ejector is OPEN, Bottom Ejector is CLOSE
2010 Dec 28 17:08:32 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Fabric-Module 5 current-status is MOD_STATUS_ERRDOWN
2010 Dec 28 17:08:32 rbx-97-n7 %PLATFORM-2-XBAR_PWRFAIL_EJECTORS_OPEN: Both ejectors open, Xbar 5 will not be powered up (Serial number JAF1446AEAN)
2010 Dec 28 17:08:35 rbx-97-n7 %PLATFORM-2-XBAR_DETECT: Xbar 5 detected (Serial number JAF1446AEAN)
2010 Dec 28 17:08:35 rbx-97-n7 %PLATFORM-5-XBAR_PWRUP: Xbar 5 powered up (Serial number JAF1446AEAN)
2010 Dec 28 17:08:35 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Fabric-Module 5 current-status is MOD_STATUS_POWERED_UP
2010 Dec 28 17:08:50 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Fabric-Module 5 current-status is MOD_STATUS_ONLINE/OK
2010 Dec 28 17:08:50 rbx-97-n7 %MODULE-5-XBAR_OK: Xbar 5 is online (serial: JAF1446AEAN)
certains ports se sont coupés. on les a remis en route.
on va inserer les cartes 32x10G
2010 Dec 28 17:12:47 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Module 4 current-status is MOD_STATUS_ERRDOWN
2010 Dec 28 17:12:47 rbx-97-n7 %PLATFORM-2-MOD_PWRFAIL_EJECTORS_OPEN: Both ejectors open, Module 4 will not be powered up (Serial number JAF1444BMNS)
2010 Dec 28 17:12:49 rbx-97-n7 %PLATFORM-2-MOD_DETECT: Module 4 detected (Serial number JAF1444BMNS) Module-Type 1/10 Gbps Ethernet Module Model N7K-F132XP-15
2010 Dec 28 17:12:49 rbx-97-n7 %PLATFORM-2-MOD_PWRUP: Module 4 powered up (Serial number JAF1444BMNS)
2010 Dec 28 17:12:49 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Module 4 current-status is MOD_STATUS_POWERED_UP
2010 Dec 28 17:13:47 rbx-97-n7 %PLTFM_CONFIG-4-XL_LICENSE_MIX_NOTIFY: Mixed use of non-XL with XL modules in the same VDC may limit common resources to non-XL capacity.
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/1 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/2 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/3 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/4 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/5 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/6 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/7 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/8 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/9 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/10 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/11 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/12 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/13 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/14 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/15 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/16 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/17 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/18 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/19 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/20 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/21 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/22 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/23 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/24 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/25 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/26 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/27 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/28 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/29 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/30 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/31 (description:) is down (None)
2010 Dec 28 17:14:40 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet4/32 (description:) is down (None)
2010 Dec 28 17:14:43 rbx-97-n7 %PLTFM_CONFIG-4-XL_LICENSE_MIX_NOTIFY: Mixed use of non-XL with XL modules in the same VDC may limit common resources to non-XL capacity.
2010 Dec 28 17:14:43 rbx-97-n7 %MODULE-5-MOD_OK: Module 4 is online (serial: JAF1444BMNS)
2010 Dec 28 17:14:43 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Module 4 current-status is MOD_STATUS_ONLINE/OK
2010 Dec 28 17:15:22 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Module 5 current-status is MOD_STATUS_ERRDOWN
2010 Dec 28 17:15:22 rbx-97-n7 %PLATFORM-2-MOD_PWRFAIL_EJECTORS_OPEN: Both ejectors open, Module 5 will not be powered up (Serial number JAF1444BMNN)
2010 Dec 28 17:15:24 rbx-97-n7 %PLATFORM-2-MOD_DETECT: Module 5 detected (Serial number JAF1444BMNN) Module-Type 1/10 Gbps Ethernet Module Model N7K-F132XP-15
2010 Dec 28 17:15:24 rbx-97-n7 %PLATFORM-2-MOD_PWRUP: Module 5 powered up (Serial number JAF1444BMNN)
2010 Dec 28 17:15:24 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Module 5 current-status is MOD_STATUS_POWERED_UP
2010 Dec 28 17:16:23 rbx-97-n7 %PLTFM_CONFIG-4-XL_LICENSE_MIX_NOTIFY: Mixed use of non-XL with XL modules in the same VDC may limit common resources to non-XL capacity.
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/1 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/2 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/3 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/4 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/5 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/6 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/7 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/8 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/9 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/10 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/11 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/12 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/13 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/14 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/15 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/16 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/17 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/18 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/19 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/20 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/21 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/22 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/23 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/24 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/25 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/26 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/27 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/28 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/29 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/30 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/31 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %ETHPORT-5-IF_DOWN_NONE: Interface Ethernet5/32 (description:) is down (None)
2010 Dec 28 17:17:31 rbx-97-n7 %PLTFM_CONFIG-4-XL_LICENSE_MIX_NOTIFY: Mixed use of non-XL with XL modules in the same VDC may limit common resources to non-XL capacity.
2010 Dec 28 17:17:31 rbx-97-n7 %MODULE-5-MOD_OK: Module 5 is online (serial: JAF1444BMNN)
2010 Dec 28 17:17:31 rbx-97-n7 %PLATFORM-5-MOD_STATUS: Module 5 current-status is MOD_STATUS_ONLINE/OK
2010 Dec 28 17:17:31 rbx-97-n7 %SYSMGR-SLOT5-5-MODULE_ONLINE: System Manager has received notification of local module becoming online.
rbx-97-n7# sh environment power
Power Supply:
Voltage: 50 Volts
Power Actual Total
Supply Model Output Capacity Status
(Watts ) (Watts )
------- ------------------- ----------- ----------- --------------
1 ------------ 0 W 0 W Absent
2 N7K-AC-6.0KW 1391 W 6000 W Ok
3 ------------ 0 W 0 W Absent
4 N7K-AC-6.0KW 1383 W 6000 W Ok
Actual Power
Module Model Draw Allocated Status
(Watts ) (Watts )
------- ------------------- ----------- ----------- --------------
1 N7K-M148GS-11L 276 W 400 W Powered-Up
2 N7K-M108X2-12L 490 W 650 W Powered-Up
3 N7K-M132XP-12 N/A 750 W Powered-Up
4 N7K-F132XP-15 308 W 385 W Powered-Up
5 N7K-F132XP-15 296 W 385 W Powered-Up
9 N7K-SUP1 N/A 210 W Powered-Up
10 N7K-SUP1 N/A 210 W Powered-Up
Xb1 N7K-C7018-FAB-1 N/A 100 W Powered-Up
Xb2 N7K-C7018-FAB-1 N/A 100 W Powered-Up
Xb3 N7K-C7018-FAB-1 N/A 100 W Powered-Up
Xb4 N7K-C7018-FAB-1 N/A 100 W Powered-Up
Xb5 N7K-C7018-FAB-1 N/A 100 W Powered-Up
fan1 N7K-C7018-FAN 217 W 736 W Powered-Up
fan2 N7K-C7018-FAN 189 W 537 W Powered-Up
N/A - Per module power not available
Power Usage Summary:
--------------------
Power Supply redundancy mode (configured) PS-Redundant
Power Supply redundancy mode (operational) PS-Redundant
Total Power Capacity (based on configured mode) 6000 W
Total Power of all Inputs (cumulative) 12000 W
Total Power Output (actual draw) 2774 W
Total Power Allocated (budget) 4763 W
Total Power Available for additional modules 1237 W
tout s'est bien deroulé. on va commencer les preparations pour les
migrations du reseau interne à Roubaix.