FS#5176 — mise à jour de vrack

Attached to Project— Reseau Internet et Baies
Maintenance
Tout le réseau
CLOSED
100%
Nous allons mettre à jour les équipements reseaux qui gerent
le vrack. Il n'y a pas de panne à prevoir. La mise à jour
soft se fait à chaud.
Date:  Tuesday, 01 March 2011, 16:48PM
Reason for closing:  Done
Comment by OVH - Monday, 28 February 2011, 16:26PM

c'est parti


Comment by OVH - Monday, 28 February 2011, 16:30PM

Nous venons de couper les robots de livraison afin de ne pas perturber la mise à jour des équipements. Les commandes sont temporairement suspendues.


Comment by OVH - Monday, 28 February 2011, 16:37PM

Compatibility check is done:
Module bootable Impact Install-type Reason
------ -------- -------------- ------------ ------
1 yes non-disruptive reset
100 yes non-disruptive rolling
101 yes non-disruptive rolling
102 yes non-disruptive rolling
103 yes non-disruptive rolling
104 yes non-disruptive rolling
105 yes non-disruptive rolling
106 yes non-disruptive rolling
107 yes non-disruptive rolling
108 yes non-disruptive rolling
109 yes non-disruptive rolling
110 yes non-disruptive rolling



Images will be upgraded according to following table:
Module Image Running-Version New-Version Upg-Required
------ ---------- ---------------------- ---------------------- ------------
1 system 4.2(1)N1(1) 5.0(2)N2(1) yes
1 kickstart 4.2(1)N1(1) 5.0(2)N2(1) yes
1 bios v1.2.0(06/19/08) v1.3.0(09/08/09) yes
100 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
101 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
102 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
103 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
104 fexth 4.2(1)N1(1) 5.0(2)N2(1) yes
105 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
106 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
107 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
108 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
109 fexth 4.2(1)N1(1) 5.0(2)N2(1) yes
110 fexth 4.2(1)N1(1) 5.0(2)N2(1) yes
1 power-seq v1.2 v1.2 no


Comment by OVH - Monday, 28 February 2011, 16:59PM

2011 Feb 28 16:40:21 cloud-1b-n5 %SATCTRL-FEX100-2-SATCTRL_IMAGE: FEX100 Image update in progress.
2011 Feb 28 16:40:31 cloud-1b-n5 %SATCTRL-FEX101-2-SATCTRL_IMAGE: FEX101 Image update in progress.
2011 Feb 28 16:40:41 cloud-1b-n5 %SATCTRL-FEX102-2-SATCTRL_IMAGE: FEX102 Image update in progress.
2011 Feb 28 16:40:51 cloud-1b-n5 %SATCTRL-FEX103-2-SATCTRL_IMAGE: FEX103 Image update in progress.
2011 Feb 28 16:41:01 cloud-1b-n5 %SATCTRL-FEX104-2-SATCTRL_IMAGE: FEX104 Image update in progress.
2011 Feb 28 16:41:11 cloud-1b-n5 %SATCTRL-FEX105-2-SATCTRL_IMAGE: FEX105 Image update in progress.
2011 Feb 28 16:41:21 cloud-1b-n5 %SATCTRL-FEX106-2-SATCTRL_IMAGE: FEX106 Image update in progress.
2011 Feb 28 16:41:31 cloud-1b-n5 %SATCTRL-FEX107-2-SATCTRL_IMAGE: FEX107 Image update in progress.
2011 Feb 28 16:41:41 cloud-1b-n5 %SATCTRL-FEX108-2-SATCTRL_IMAGE: FEX108 Image update in progress.
2011 Feb 28 16:41:51 cloud-1b-n5 %SATCTRL-FEX109-2-SATCTRL_IMAGE: FEX109 Image update in progress.
2011 Feb 28 16:42:01 cloud-1b-n5 %SATCTRL-FEX110-2-SATCTRL_IMAGE: FEX110 Image update in progress.
2011 Feb 28 16:42:05 cloud-1b-n5 %SATCTRL-FEX101-2-SATCTRL_IMAGE: FEX101 Image update failed [/isan/plugin_img/fex.bin]: File transfer error
2011 Feb 28 16:42:16 cloud-1b-n5 %SATCTRL-FEX100-2-SATCTRL_IMAGE: FEX100 Image update failed [/isan/plugin_img/fex.bin]: File transfer error
2011 Feb 28 16:42:20 cloud-1b-n5 %SATCTRL-FEX102-2-SATCTRL_IMAGE: FEX102 Image update failed [/isan/plugin_img/fex.bin]: File transfer error
2011 Feb 28 16:42:21 cloud-1b-n5 %DAEMON-3-SYSTEM_MSG: tftpd: read(ack): Connection refused - in.tftpd[4669]
2011 Feb 28 16:42:21 cloud-1b-n5 %DAEMON-3-SYSTEM_MSG: tftpd: read(ack): Connection refused - in.tftpd[4672]
2011 Feb 28 16:42:22 cloud-1b-n5 %DAEMON-3-SYSTEM_MSG: tftpd: read(ack): Connection refused - in.tftpd[4677]
2011 Feb 28 16:42:22 cloud-1b-n5 %DAEMON-3-SYSTEM_MSG: tftpd: read(ack): Connection refused - in.tftpd[4541]
2011 Feb 28 16:42:23 cloud-1b-n5 %DAEMON-3-SYSTEM_MSG: tftpd: read(ack): Connection refused - in.tftpd[4680]
2011 Feb 28 16:42:23 cloud-1b-n5 %DAEMON-3-SYSTEM_MSG: tftpd: read(ack): Connection refused - in.tftpd[4686]
2011 Feb 28 16:42:24 cloud-1b-n5 %DAEMON-3-SYSTEM_MSG: tftpd: read(ack): Connection refused - in.tftpd[4682]
2011 Feb 28 16:42:25 cloud-1b-n5 %DAEMON-3-SYSTEM_MSG: tftpd: read(ack): Connection refused - in.tftpd[4664]
2011 Feb 28 16:42:26 cloud-1b-n5 %DAEMON-3-SYSTEM_MSG: tftpd: read(ack): Connection refused - in.tftpd[4665]
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 100 is online
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 101 is online
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 102 is online
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 103 is online
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 104 is online
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 105 is online
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 106 is online
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 108 is online
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 109 is online
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 110 is online
2011 Feb 28 16:43:26 cloud-1b-n5 %PFMA-2-FEX_STATUS: Fex 107 is online
2011 Feb 28 16:43:56 cloud-1b-n5 %SATCTRL-FEX107-2-SATCTRL_IMAGE: FEX107 Image update failed [/isan/plugin_img/fex.bin]: File transfer error
2011 Feb 28 16:44:12 cloud-1b-n5 %SATCTRL-FEX106-2-SATCTRL_IMAGE: FEX106 Image update failed [/isan/plugin_img/fex.bin]: File transfer error
2011 Feb 28 16:46:42 cloud-1b-n5 %SATCTRL-FEX104-2-SATCTRL_IMAGE: FEX104 Image update complete.
2011 Feb 28 16:47:24 cloud-1b-n5 %SATCTRL-FEX103-2-SATCTRL_IMAGE: FEX103 Image update complete.
2011 Feb 28 16:47:36 cloud-1b-n5 %SATCTRL-FEX108-2-SATCTRL_IMAGE: FEX108 Image update complete.
2011 Feb 28 16:48:04 cloud-1b-n5 %SATCTRL-FEX109-2-SATCTRL_IMAGE: FEX109 Image update complete.
2011 Feb 28 16:48:17 cloud-1b-n5 %SATCTRL-FEX105-2-SATCTRL_IMAGE: FEX105 Image update complete.
2011 Feb 28 16:48:18 cloud-1b-n5 %SATCTRL-FEX110-2-SATCTRL_IMAGE: FEX110 Image update complete.
2011 Feb 28 16:48:42 cloud-1b-n5 %SYSMGR-3-SERVICE_TERMINATED: Service "installer" (PID 4463) has finished with error code SYSMGR_EXITCODE_FAILURE_NOCALLHOME (20).

pas top ... bon ...


Comment by OVH - Monday, 28 February 2011, 17:02PM

c'est reparti

Compatibility check is done:
Module bootable Impact Install-type Reason
------ -------- -------------- ------------ ------
1 yes non-disruptive none
100 yes non-disruptive rolling
101 yes non-disruptive rolling
102 yes non-disruptive rolling
103 yes non-disruptive rolling
104 yes non-disruptive rolling
105 yes non-disruptive rolling
106 yes non-disruptive rolling
107 yes non-disruptive rolling
108 yes non-disruptive rolling
109 yes non-disruptive rolling
110 yes non-disruptive rolling



Images will be upgraded according to following table:
Module Image Running-Version New-Version Upg-Required
------ ---------- ---------------------- ---------------------- ------------
1 system 5.0(2)N2(1) 5.0(2)N2(1) no
1 kickstart 5.0(2)N2(1) 5.0(2)N2(1) no
1 bios v1.3.0(09/08/09) v1.3.0(09/08/09) no
100 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
101 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
102 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
103 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
104 fexth 4.2(1)N1(1) 5.0(2)N2(1) yes
105 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
106 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
107 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
108 fex 4.2(1)N1(1) 5.0(2)N2(1) yes
109 fexth 4.2(1)N1(1) 5.0(2)N2(1) yes
110 fexth 4.2(1)N1(1) 5.0(2)N2(1) yes
1 power-seq v1.2 v1.2 no



Comment by OVH - Monday, 28 February 2011, 17:34PM

Rien à faire. La mise à jour ne veut pas passer.


Comment by OVH - Monday, 28 February 2011, 17:38PM

Le FEX de type N2K-C2148T-1GE pose les problemes
alors que N2K-C2248TP-1GE et N2K-C2232PP-10GE
passent sans probleme.


Comment by OVH - Monday, 28 February 2011, 20:13PM

La mise à jour ne se passe pas comme prevue. On a un type
d'équipement qui ne supporte (apparament) pas la mise à
jour à chaud. Ou pas bien ? E tout cas c'est pas comme
sur les toutes les mises à jour qui ont generé 0 downtime.

On va devoir donc mettre à jour cette nuit à froid donc
avec une coupure d'environ 1-3 minutes le temps de faire
rebooter l'équipement en question et qu'il se mette à jour.
Il y a 10 équipements qu'on va faire 1 par 1.

Enfin, comme il s'agit d'un probleme qu'on n'a pas vu avant
et on ne peut pas reproduire en labo (on n'a plus en stock
cette serie d'équipement) 1-3 minutes dans le meilleur de cas
par équipement.

On va voir tout ceci à partir de minuit.


Comment by OVH - Monday, 28 February 2011, 22:47PM

on commence les inter


Comment by OVH - Monday, 28 February 2011, 22:48PM

107


Comment by OVH - Monday, 28 February 2011, 22:59PM

up. on est sur un 10 minutes

02/28/2011 16:41:31.488614: Module image preload in progress
02/28/2011 16:43:56.901311: Image preload failed.
02/28/2011 17:04:28.113188: Module image preload in progress
02/28/2011 17:06:16.576703: Image preload failed.
02/28/2011 17:18:07.117728: Module image preload in progress
02/28/2011 17:20:16.268380: Image preload failed.
02/28/2011 22:48:53.994886: Deleting route to FEX
02/28/2011 22:48:54.2982: Module disconnected
02/28/2011 22:48:54.4897: Deleting route to FEX
02/28/2011 22:48:54.12115: Module disconnected
02/28/2011 22:48:54.13725: Offlining Module
02/28/2011 22:48:54.14987: Module Offline Sequence
02/28/2011 22:49:08.446975: Module Offline
02/28/2011 22:49:50.449257: Module register received
02/28/2011 22:49:50.450425: Image Version Mismatch
02/28/2011 22:49:50.450642: Registration response sent
02/28/2011 22:49:50.459206: Requesting satellite to download image
02/28/2011 22:55:44.210603: Image preload successful.
02/28/2011 22:55:59.963878: Deleting route to FEX
02/28/2011 22:55:59.973338: Module disconnected
02/28/2011 22:55:59.975094: Module Offline
02/28/2011 22:56:00.1899: Deleting route to FEX
02/28/2011 22:56:00.9762: Module disconnected
02/28/2011 22:56:00.25746: Offlining Module
02/28/2011 22:56:00.57518: Deleting route to FEX
02/28/2011 22:56:00.64890: Module disconnected
02/28/2011 22:56:00.68033: Offlining Module
02/28/2011 22:57:40.721946: Module register received
02/28/2011 22:57:40.723457: Registration response sent
02/28/2011 22:57:41.255604: Module Online Sequence
02/28/2011 22:58:08.719736: Module Online


Comment by OVH - Monday, 28 February 2011, 23:01PM

100, 101, 102, 103


Comment by OVH - Monday, 28 February 2011, 23:02PM

pas terrible. un download à la fois ...


Comment by OVH - Monday, 28 February 2011, 23:03PM

non, c'est bon, plusieurs Image Download en même temps.


Comment by OVH - Monday, 28 February 2011, 23:05PM

cloud-1b-n5(config-if-range)# sh fex
FEX FEX FEX FEX
Number Description State Model
-------------------------------------------------------------
100 fex100|20A02 Image Download N2K-C2148T-1GE
101 fex101|25C01 Image Download N2K-C2148T-1GE
102 fex102|25C01 Image Download N2K-C2148T-1GE
103 fex103|00E03 Image Download N2K-C2148T-1GE
104 fex104|00B05 Online N2K-C2248TP-1GE
105 fex105|00C04 Online N2K-C2148T-1GE
106 fex106|00F03 Online N2K-C2148T-1GE
107 fex107|40B02 Online N2K-C2148T-1GE
108 fex108|00E04 Online N2K-C2148T-1GE
109 fex109|salle20|20A04 Online N2K-C2232PP-10GE
110 fex110|salle40|40B02 Online N2K-C2248TP-1GE


Comment by OVH - Monday, 28 February 2011, 23:11PM

101 up
02/28/2011 23:01:17.129476: Deleting route to FEX
02/28/2011 23:01:17.139545: Module disconnected
02/28/2011 23:01:17.141266: Deleting route to FEX
02/28/2011 23:01:17.148518: Module disconnected
02/28/2011 23:01:17.149663: Offlining Module
02/28/2011 23:01:17.150580: Module Offline Sequence
02/28/2011 23:01:46.207686: Module Offline
02/28/2011 23:02:32.6251: Module register received
02/28/2011 23:02:32.7242: Image Version Mismatch
02/28/2011 23:02:32.7359: Registration response sent
02/28/2011 23:02:32.18822: Requesting satellite to download image
02/28/2011 23:07:38.231591: Image preload successful.
02/28/2011 23:07:55.566098: Deleting route to FEX
02/28/2011 23:07:55.573678: Module disconnected
02/28/2011 23:07:55.575430: Module Offline
02/28/2011 23:07:55.605235: Deleting route to FEX
02/28/2011 23:07:55.612806: Module disconnected
02/28/2011 23:07:55.616081: Offlining Module
02/28/2011 23:07:55.660683: Deleting route to FEX
02/28/2011 23:07:55.668111: Module disconnected
02/28/2011 23:07:55.671084: Offlining Module
02/28/2011 23:09:53.521046: Module register received
02/28/2011 23:09:53.522341: Registration response sent
02/28/2011 23:09:54.60435: Module Online Sequence
02/28/2011 23:10:24.728095: Module Online


Comment by OVH - Monday, 28 February 2011, 23:11PM

100:
02/28/2011 23:01:17.931733: Deleting route to FEX
02/28/2011 23:01:17.947186: Module disconnected
02/28/2011 23:01:17.948739: Deleting route to FEX
02/28/2011 23:01:17.998764: Module disconnected
02/28/2011 23:01:18.27: Offlining Module
02/28/2011 23:01:18.2990: Module Offline Sequence
02/28/2011 23:01:46.231926: Module Offline
02/28/2011 23:03:03.700256: Module register received
02/28/2011 23:03:03.701273: Image Version Mismatch
02/28/2011 23:03:03.701399: Registration response sent
02/28/2011 23:03:03.710108: Requesting satellite to download image
02/28/2011 23:08:28.859570: Image preload successful.
02/28/2011 23:08:44.77919: Deleting route to FEX
02/28/2011 23:08:44.85736: Module disconnected
02/28/2011 23:08:44.88294: Module Offline
02/28/2011 23:08:44.125213: Deleting route to FEX
02/28/2011 23:08:44.132639: Module disconnected
02/28/2011 23:08:44.135347: Offlining Module
02/28/2011 23:08:44.177394: Deleting route to FEX
02/28/2011 23:08:44.184842: Module disconnected
02/28/2011 23:08:44.187365: Offlining Module
02/28/2011 23:10:24.363880: Module register received
02/28/2011 23:10:24.365211: Registration response sent
02/28/2011 23:10:24.898032: Module Online Sequence
02/28/2011 23:10:51.947184: Module Online


Comment by OVH - Monday, 28 February 2011, 23:12PM

102:
02/28/2011 23:01:16.325663: Deleting route to FEX
02/28/2011 23:01:16.334013: Module disconnected
02/28/2011 23:01:16.335544: Deleting route to FEX
02/28/2011 23:01:16.342941: Module disconnected
02/28/2011 23:01:16.344090: Offlining Module
02/28/2011 23:01:16.344994: Module Offline Sequence
02/28/2011 23:01:46.268741: Module Offline
02/28/2011 23:01:50.949282: Module register received
02/28/2011 23:01:50.950257: Image Version Mismatch
02/28/2011 23:01:50.950367: Registration response sent
02/28/2011 23:01:50.960068: Requesting satellite to download image
02/28/2011 23:07:21.684099: Image preload successful.
02/28/2011 23:07:37.816515: Deleting route to FEX
02/28/2011 23:07:37.826998: Module disconnected
02/28/2011 23:07:37.828654: Module Offline
02/28/2011 23:07:37.887625: Deleting route to FEX
02/28/2011 23:07:37.895639: Module disconnected
02/28/2011 23:07:37.906713: Offlining Module
02/28/2011 23:07:37.940569: Deleting route to FEX
02/28/2011 23:07:37.948708: Module disconnected
02/28/2011 23:07:37.951885: Offlining Module
02/28/2011 23:09:18.378267: Module register received
02/28/2011 23:09:18.379569: Registration response sent
02/28/2011 23:09:18.911134: Module Online Sequence
02/28/2011 23:09:45.789403: Module Online


Comment by OVH - Monday, 28 February 2011, 23:12PM

103:
02/28/2011 23:01:15.394550: Deleting route to FEX
02/28/2011 23:01:15.403155: Module disconnected
02/28/2011 23:01:15.405094: Deleting route to FEX
02/28/2011 23:01:15.415304: Module disconnected
02/28/2011 23:01:15.416645: Offlining Module
02/28/2011 23:01:15.417601: Module Offline Sequence
02/28/2011 23:01:46.143179: Module Offline
02/28/2011 23:03:41.54911: Module register received
02/28/2011 23:03:41.55898: Image Version Mismatch
02/28/2011 23:03:41.56017: Registration response sent
02/28/2011 23:03:41.67531: Requesting satellite to download image
02/28/2011 23:08:55.813565: Image preload successful.
02/28/2011 23:09:11.294618: Deleting route to FEX
02/28/2011 23:09:11.316212: Module disconnected
02/28/2011 23:09:11.319013: Module Offline
02/28/2011 23:09:11.339625: Deleting route to FEX
02/28/2011 23:09:11.348376: Module disconnected
02/28/2011 23:09:11.350873: Offlining Module
02/28/2011 23:09:11.400175: Deleting route to FEX
02/28/2011 23:09:11.408110: Module disconnected
02/28/2011 23:09:11.410710: Offlining Module
02/28/2011 23:10:55.697871: Module register received
02/28/2011 23:10:55.699150: Registration response sent
02/28/2011 23:10:56.248764: Module Online Sequence
02/28/2011 23:11:23.831624: Module Online


Comment by OVH - Monday, 28 February 2011, 23:13PM

105,106,108


Comment by OVH - Monday, 28 February 2011, 23:22PM

108: up
02/28/2011 23:13:16.659772: Deleting route to FEX
02/28/2011 23:13:16.667174: Module disconnected
02/28/2011 23:13:16.668717: Deleting route to FEX
02/28/2011 23:13:16.676241: Module disconnected
02/28/2011 23:13:16.677497: Offlining Module
02/28/2011 23:13:16.678461: Module Offline Sequence
02/28/2011 23:13:56.454277: Module Offline
02/28/2011 23:14:02.346991: Module register received
02/28/2011 23:14:02.347976: Image Version Mismatch
02/28/2011 23:14:02.348095: Registration response sent
02/28/2011 23:14:02.357064: Requesting satellite to download image
02/28/2011 23:19:04.297376: Image preload successful.
02/28/2011 23:19:21.113000: Deleting route to FEX
02/28/2011 23:19:21.120607: Module disconnected
02/28/2011 23:19:21.122301: Module Offline
02/28/2011 23:19:21.153038: Deleting route to FEX
02/28/2011 23:19:21.161373: Module disconnected
02/28/2011 23:19:21.163916: Offlining Module
02/28/2011 23:19:21.215645: Deleting route to FEX
02/28/2011 23:19:21.223132: Module disconnected
02/28/2011 23:19:21.225972: Offlining Module
02/28/2011 23:21:01.452135: Module register received
02/28/2011 23:21:01.453408: Registration response sent
02/28/2011 23:21:01.675645: Module Online Sequence
02/28/2011 23:21:29.509689: Module Online


Comment by OVH - Monday, 28 February 2011, 23:23PM

106: up
02/28/2011 23:13:18.153540: Deleting route to FEX
02/28/2011 23:13:18.161159: Module disconnected
02/28/2011 23:13:18.163105: Deleting route to FEX
02/28/2011 23:13:18.180811: Module disconnected
02/28/2011 23:13:18.181901: Offlining Module
02/28/2011 23:13:18.182778: Module Offline Sequence
02/28/2011 23:13:57.39114: Module Offline
02/28/2011 23:15:53.785707: Module register received
02/28/2011 23:15:53.786738: Image Version Mismatch
02/28/2011 23:15:53.786860: Registration response sent
02/28/2011 23:15:53.796040: Requesting satellite to download image
02/28/2011 23:20:43.597792: Image preload successful.
02/28/2011 23:21:00.306001: Deleting route to FEX
02/28/2011 23:21:00.313451: Module disconnected
02/28/2011 23:21:00.315127: Module Offline
02/28/2011 23:21:00.345386: Deleting route to FEX
02/28/2011 23:21:00.352948: Module disconnected
02/28/2011 23:21:00.356469: Offlining Module
02/28/2011 23:21:00.416404: Deleting route to FEX
02/28/2011 23:21:00.424884: Module disconnected
02/28/2011 23:21:00.427329: Offlining Module
02/28/2011 23:22:40.732535: Module register received
02/28/2011 23:22:40.733821: Registration response sent
02/28/2011 23:22:40.995007: Module Online Sequence
02/28/2011 23:23:08.963722: Module Online


Comment by OVH - Monday, 28 February 2011, 23:24PM

105 up
02/28/2011 23:13:19.462460: Deleting route to FEX
02/28/2011 23:13:19.471097: Module disconnected
02/28/2011 23:13:19.473100: Deleting route to FEX
02/28/2011 23:13:19.482795: Module disconnected
02/28/2011 23:13:19.483923: Offlining Module
02/28/2011 23:13:19.484820: Module Offline Sequence
02/28/2011 23:13:57.18916: Module Offline
02/28/2011 23:15:15.289667: Module register received
02/28/2011 23:15:15.290642: Image Version Mismatch
02/28/2011 23:15:15.290760: Registration response sent
02/28/2011 23:15:15.299115: Requesting satellite to download image
02/28/2011 23:20:54.557415: Image preload successful.
02/28/2011 23:21:09.469765: Deleting route to FEX
02/28/2011 23:21:09.477274: Module disconnected
02/28/2011 23:21:09.479010: Module Offline
02/28/2011 23:21:09.509092: Deleting route to FEX
02/28/2011 23:21:09.516864: Module disconnected
02/28/2011 23:21:09.519378: Offlining Module
02/28/2011 23:21:09.571852: Deleting route to FEX
02/28/2011 23:21:09.579704: Module disconnected
02/28/2011 23:21:09.582199: Offlining Module
02/28/2011 23:23:18.760250: Module register received
02/28/2011 23:23:18.761914: Registration response sent
02/28/2011 23:23:18.950577: Module Online Sequence
02/28/2011 23:23:47.432548: Module Online


Comment by OVH - Monday, 28 February 2011, 23:24PM

il reste 3 modules. on va les mettre maintenant à chaud.


Comment by OVH - Tuesday, 01 March 2011, 00:11AM

mis à jour.

le A ne ping pas. il fonctionne, pas de probleme mais ne ping pas.
le B ping ...


Comment by OVH - Tuesday, 01 March 2011, 00:11AM

on reactive la double attach


Comment by OVH - Tuesday, 01 March 2011, 00:20AM

voilà tout est up ... ouff ! quelle avanture !


Comment by OVH - Tuesday, 01 March 2011, 16:09PM

on a de problemes pour activer les nouveaux vrack.
nous allons couper l'un de 2 côtés et le redemarrer.


Comment by OVH - Tuesday, 01 March 2011, 16:30PM

Le probleme:
Local suspended VLANs - 2009,2174,2215,2241 -

Le B en reboot. Pendant le reboot:
Local suspended VLANs - - -


Comment by OVH - Tuesday, 01 March 2011, 16:35PM

up. il a generé 30 secondes de coupure quand il s'est
reactivé. on est intervenu pour le recouper. c'est pas
automatique automatique ...

là on le reactive.


Comment by OVH - Tuesday, 01 March 2011, 16:48PM

up.

et le probleme est fixé:
Local suspended VLANs - - -

On aurait dû aller jusqu'au bout de la demarche hier et forcer
le redemarrage du B car il ne pingait pas. il se peut que le B
a un probleme hard et c'est pour ça qu'on n'a pas pu mettre
tout à chaud ?

On saura quand on mettra à jour la nouvelle version. On le fera
sur le A.