FS#5427 — réseau 46.105.104 et 46.105.106

Attached to Project— Reseau Internet et Baies
Maintenance
Tout le réseau
CLOSED
100%
Un bug au niveau du NX-OS empêche les robots de livraison de configurer correctement les switchs. Nous allons tenter un downgrade des switchs de ce réseau pour fixer le propblème.
Date:  Monday, 09 May 2011, 21:10PM
Reason for closing:  Done
Comment by OVH - Monday, 09 May 2011, 16:58PM

On va demarrer la mise à jour


Comment by OVH - Monday, 09 May 2011, 18:47PM

la maj est terminée.


Comment by OVH - Monday, 09 May 2011, 19:20PM

46.105.106: fait


Comment by OVH - Monday, 09 May 2011, 20:07PM

Pre-loading modules.
[This step might take upto 20 minutes to complete - please wait.]
[*Warning -- Please do not abort installation/reload or powercycle fexes*]
[####################] 100% -- SUCCESS

Module 100: Non-disruptive upgrading.
[# ] 0% -- FAIL. Return code 0x401D0039 (Disruptive image upgrade failed because module is not up).

Install has failed. Return code 0x40930020 (Non-disruptive upgrade of a module failed).
Please identify the cause of the failure, and try 'install all' again.


05/05/2011 16:34:05.299713: Module register received
05/05/2011 16:34:05.309568: Registration response sent
05/05/2011 16:34:05.445900: Module Online Sequence
05/05/2011 16:34:07.806437: Module Online
05/09/2011 19:22:52.539422: Module image preload in progress
05/09/2011 19:27:54.480246: Image preload successful.
05/09/2011 19:31:50.493274: LC ug rdy failed


Comment by OVH - Monday, 09 May 2011, 20:20PM

n5.46.105.104.249# sh fex
FEX FEX FEX FEX
Number Description State Model Serial
------------------------------------------------------------------------
100 fex100|51C24 Check Upg Seq N2K-C2248TP-1GE JAF1453AGSM

on lance une upgrade urgente


Comment by OVH - Monday, 09 May 2011, 20:44PM

pas moyen de le mettre à jour. on va le rebooter en hard
et forcer la mise à jour.


Comment by OVH - Monday, 09 May 2011, 20:49PM

up. 30 minutes de panne. envie de se pendre.