Incident Report for Network & Infrastructure
Resolved
Nous avons un probleme avec la carte Sup numero 5 d'un Nexus 7010 gérant l'infrastructure pCC.

%DIAGCLIENT-STANDBY-2-EEM_ACTION_HM_SHUTDOWN: Test has been disabled as a part of default EEM action
%DEVICE_TEST-STANDBY-2-PWR_MGMT_BUS_FAIL: Module 5 has failed test SpineControlBus 20 times on device Power Mgmt Bus on slot 11 due to error Spine control test failed error number 0x00000002

Nous investiguons avec Cisco sur l'origine de ce log.

Update(s):

Date: 2012-03-20 17:29:04 UTC
Nous avons redémarré la supervisor numéro 5. Les tests sont bons.

#sh diagnostic result module 5 test SpineControlBus detail

Current bootup diagnostic level: complete
Module 5: Supervisor module-1X (Standby)

Diagnostic level at card bootup: complete

Test results: (. = Pass, F = Fail, I = Incomplete,
U = Untested, A = Abort, E = Error disabled)

______________________________________________________________________

11) SpineControlBus .

Error code ------------------> DIAG TEST SUCCESS
Total run count -------------> 1814
Last test execution time ----> Tue Mar 20 18:29:56 2012
First test failure time -----> n/a
Last test failure time ------> n/a
Last test pass time ---------> Tue Mar 20 18:29:56 2012
Total failure count ---------> 0
Consecutive failure count ---> 0
Last failure reason ---------> No failures yet
Next Execution time ---------> Tue Mar 20 18:30:26 2012



Date: 2012-02-20 12:23:40 UTC
Cisco sont en observation sur le probleme. Il n'y a pas d'impact sur le trafic.
Posted Feb 13, 2012 - 11:47 UTC